You are here: Home » Products » Mineral Insulated Cable » Mineral insulated thermocouple cable » Simplex Mineral Insulated Thermocouple Cable (MI Cable) with Stainless steel SS316

loading

Share to:
facebook sharing button
twitter sharing button
line sharing button
wechat sharing button
linkedin sharing button
pinterest sharing button
whatsapp sharing button
sharethis sharing button

Simplex Mineral Insulated Thermocouple Cable (MI Cable) with Stainless steel SS316

. Simplex mineral insulated thermocouple cable
. Differnet sheath diameters from 0.25mm to 12.7mm
. Sheath material: SS316
. Standard no. of conductors: 2 conductors
. Internal conductors: Thermocouple J, K, T, E, N
. MI cables with high reliability and high heat resistance
. MI cables withstands vibration and pressures
Quantity:

Technical Data


Feature
. Mineral insulated cables are the industry standard, proven choice for high temperature probe fabrication.
. Bulk MI cable is rugged, inexpensive, reliable, widely accepted by industry, and readily available in standard configurations, the metal sheath provides a self-armoured cable, which is mechanically robust even at small diameters.
. The small mass and high thermal conductivity of a properly made cable promotes rapid response of the finished thermocouple assembly.
. Sheath materials can be selected to offer strong resistance against corrosive environments and extremely high temperature effects.

Sheath Material of SS316
Applications
: Chemical instrument construction, nuclear power plants, reactor instrumentation, furnace construction, sulphite, chemical pulp, textile, dye, fatty acid, photochemical and pharmaceutical industries.
Max. continuous temperature: 925°C
Heat resistance: Good oxidation resistance in intermittent service to 800°C and in continuous service to 925°C. 
Corrosion resistance: Good resistance to a wide range of chemicals. Highly resistant to complex sulphur compounds used in pulp and paper processing. Also resists attack of marine and corrosive industrial atmospheres.
Welding: Good characteristics suited to all standard welding methods.

Chemical Composition of Stainless Steel Sheath                 

       

Sheath Material

     

Chemical Composition

Max. Temp. In Air Melting Temp.
C Si Mn P S Cr Ni

Others

SS316 ≤0.08 ≤1.00

≤2.00

≤0.035 ≤0.03 16-19

11-14

Mo: 1.8-2.5

925℃

1370℃


Sheath Specification                                                
 Outside sheath diameter   ±0.05mm or ±1% of nominal diameter
 Wall thickness  10% of sheath diameter as a minimum
 Wire diameter  15% of sheath diameter as a minimum for 2 wires,
 12% of sheath diameter as a minimum for 4 wires,
 9% of sheath diameter as a minimum for 6 wires. 
 Calibration  To meet special limits of error as defined in ASTM-E230 and IEC 60584-2
 MgO purity  99.6% MgO powder

 Sheath material    

 Sheath OD (mm)      Wall Thickness (mm)   

 Wire Dia. (mm)     

 Coil Length(m)    
         SS316  0.5  0.05-0.10  0.08-0.12     

 200     

 1.0 

 0.10-0.20      0.15-0.20      200    
 1.5   

 0.15-0.25   

 0.23-0.30     

 200   

 1.6      0.16-0.26     0.26-0.36     200    
 2.0    

 0.20-0.35    

 0.30-0.50     

 100     

 2.4    

 0.24-0.36     

 0.36-0.41     

 100    

 3.0

 0.30-0.48

 0.45-0.60

 100     

 3.2

 0.32-0.58     

 0.48-0.68     

 100     

 4.0    

 0.40-0.62     

 0.60-0.70       70     

 4.5     

 0.45-0.68     

 0.68-0.77     

 70     

 4.8     

 0.48-0.83     

 0.72-0.85     

 70     

 6.0     

 0.60-1.08     

 0.90-1.10     

 50     

 6.4     

 0.64-1.15     

 0.92-1.12     

 40     

 8.0     

 0.80-1.44     

 1.20-1.40     

 30     

 9.5     

 0.95-1.43     

 1.43-1.62     

 20     

 10.0     

1.00-1.50     

 1.50-1.70     

 20     

 10.8     

 1.08-1.62       1.62-1.84     

 20     

 12.7     

 1.27-1.90     

 1.91-2.05     

 10     


Calibration Tolerance

  Calibration

 Tolerance     

 Special Limits (Grade I)

 Standard Limits (Grade II)      Temperature Range (℃)     

 K (Chromel vs Alumel)     

 ±1.5°C or ±0.4%   ±2.5°C or ±0.75%  -40~1000     

 J (Iron vs Constantan)     

 -40~750     

 E (Chromel vs Constantan)

 -40~800

 T (Copper vs Constantan)

 ±1°C or ±0.75%  -40~350


Order Code


Order Code of Mineral Insulated Thermocouple Cable (MI Cable):  

 Calibration    

Sheath OD (mm)    

Sheath Material    

 Type K     

 Type J     

 Type E     

 Type T     

 MIC-K-0.5-SS316  MIC-J-0.5-SS316

 MIC-E-0.5-SS316

 MIC-T-0.5-SS316

 0.5

 SS316

 MIC-K-1.0-SS316  MIC-J-1.0-SS316  MIC-E-1.0-SS316  MIC-T-1.0-SS316  1.0   SS316

 MIC-K-1.5-SS316

 MIC-J-1.5-SS316

 MIC-E-1.5-SS316

 MIC-T-1.5-SS316

 1.5

 SS316

 MIC-K-1.6-SS316

 MIC-J-1.6-SS316 

 MIC-E-1.6-SS316

 MIC-T-1.6-SS316

 1.6

 SS316
 MIC-K-2.0-SS316  MIC-J-2.0-SS316

 MIC-E-2.0-SS316

 MIC-T-2.0-SS316

 2.0 

 SS316 

 MIC-K-2.4-SS316  MIC-J-2.4-SS316  MIC-E-2.4-SS316  MIC-T-2.4-SS316  2.4  SS316
 MIC-K-3.0-SS316  MIC-J-3.0-SS316  MIC-E-3.0-SS316  MIC-T-3.0-SS316  3.0  SS316
 MIC-K-3.2-SS316  MIC-J-3.2-SS316  MIC-E-3.2-SS316  MIC-T-3.2-SS316  3.2  SS316
 MIC-K-4.0-SS316  MIC-J-4.0-SS316  MIC-E-4.0-SS316  MIC-T-4.0-SS316  4.0  SS316
 MIC-K-4.5-SS316  MIC-J-4.5-SS316  MIC-E-4.5-SS316  MIC-T-4.5-SS316  4.5  SS316
 MIC-K-4.8-SS316  MIC-J-4.8-SS316  MIC-E-4.8-SS316  MIC-T-4.8-SS316  4.8  SS316
 MIC-K-5.0-SS316  MIC-J-5.0-SS316  MIC-E-5.0-SS316  MIC-T-5.0-SS316  5.0  SS316
 MIC-K-6.0-SS316  MIC-J-6.0-SS316  MIC-E-6.0-SS316  MIC-T-6.0-SS316  6.0  SS316
 MIC-K-6.4-SS316  MIC-J-6.4-SS316  MIC-E-6.4-SS316  MIC-T-6.4-SS316  6.4  SS316
 MIC-K-8.0-SS316  MIC-J-8.0-SS316  MIC-E-8.0-SS316  MIC-T-8.0-SS316  8.0  SS316
 MIC-K-9.5-SS316  MIC-J-9.5-SS316  MIC-E-9.5-SS316  MIC-T-9.5-SS316  9.5  SS316
 MIC-K-10.0-SS316  MIC-J-10.0-SS316  MIC-E-10.0-SS316  MIC-T-10.0-SS316  10.0  SS316
 MIC-K-10.8-SS316  MIC-J-10.8-SS316  MIC-E-10.8-SS316  MIC-T-10.8-SS316  10.8  SS316
 MIC-K-12.7-SS316  MIC-J-12.7-SS316  MIC-E-12.7-SS316  MIC-T-12.7-SS316  12.7  SS316

Order Example:
 1. MIC-K-0.5-SS316, it means you order MI thermocouple cable is Simplex, type K, sheath dia: 0.5mm, sheath material: SS316.
 2. If you order MI thermocouple cable is Duplex, please change "MIC" to "MICD", it means "MICD-K-0.5-SS316".
 3. If you order MI thermocouple cable is Triple, please change "MIC" to "MICT", it means "MICT-K-0.5-SS316".
 4. If you order MI thermcouple cable is special limits, please change calibration "K" to "KK", it means "MIC-KK-0.5-SS316".
 5. For other calibration such as type N is also available.
 

Previous: 
Next: 
Feedback

Navigations

Product Categories

Contact Us

   +86-577-61731117
   +86-577-61731116
   +86-13868772123
   +86-13868772123

Get In Touch

Check our privacy policy on how we collect and process your information.
Copyright 2022 © Zhejiang Zonzen Electric Co., Ltd. All Rights Reserved. Sitemap. Privacy Policy