Feature
Characteristics | Insulation | Jacket |
Abrasion Resistance | Excellent | Excellent |
Cut Through Resistance | Good | Good |
Moisture Resistance | Excellent | Excellent |
Solvent Resistance | Good | Good |
Service Temperature | 200°C continuous 250°C single | 200°C continuous 250°C single |
Flame Test | Non-flammable | Non-flammable |
Specification
Item | Specification |
Model | KX-FEP-FEP-D-SSB-FEP-20S |
Calibration | Type KX |
+ Chromel - Alumel | |
Wire size | 20AWG, 2*7/0.3MM |
Wire type | Stranded |
Construction | Parallel conductors |
Number of pair | Single |
Insulation | FEP |
Jacket | FEP |
Drain | 20AWG tinned copper drain wire |
Inner shield | Stainless steel |
Overall | FEP |
Tolerance | Standard limits of error |
Max. Operating temperature | 200°C |
Color code | ANSI |
Packing | Roll or spool (As required) |
Drawing
Technical Data
Thermocouple extension type | ANSI Color Code | Initial Calibration Tolerances | ||||
Wire Alloys | Calibration | Conductor (+/-) | Jacket | Temperature Range | Standard | Special |
Iron (+) vs. Constantan(-) | JX | White/Red | Black | 0°C to +200°C | ± 2.2°C | ± 1.1°C |
Chromel (+) vs. Alumel (-) | KX | Yellow/Red | Yellow | 0°C to +200°C | ± 2.2°C | ± 1.1°C |
Copper(+) vs. Constantan(-) | TX | Blue/Red | Blue | -60°C to +100°C | ± 1.1°C | ± 0.5°C |
Chromel(+) vs. Constantan(-) | EX | Purple/Red | Purple | 0°C to +200°C | ± 1.7°C | ± 1.1°C |
Nirosil (+) vs. Nisil (-) | NX | Orange/Red | Orange | 0°C to +200°C | ± 2.2°C | ± 1.1°C |
Copper (+) vs. Alloy 11 (-) | RX/SX | Black/Red | Green | 0°C to +200°C | ± 5°C | - |
Copper S (+) vs. -Copper E (-) | BX | Gray/Red | Gray | 0°C to +200°C | ± 3.7°C | - |