Technical Data
SS304
Maximum temperature: 900°C (1650°F). Most widely used low temperature sheath material. Extensively used in food, beverage, chemical and other industries where corrosion resistance is required. Subject to damaging carbide precipitation in 482°C to 871°C (900° to 1600°F) range. Lowest cost corrosion resistant sheath material available.
SS321
Maximum temperature: 871°C (1600°F). Similar to 304 SS except titanium stabilized for intergranular corrosion. This alloy is designed to overcome susceptibility to carbide precipitation in the 482° to 871°C (900° to 1600°F) range. Used in aerospace and chemical applications.
SS316
Maximum temperature: 900°C (1650°F). Best corrosion resistance of the austenitic stainless steel grades. Good corrosion resistance in H2S. Widely used in the food and chemical industry. Subject to damaging carbide precipitation in 482° to 871°C (900° to 1600°F) range.
SS310
Maximum temperature: 1150°C (2100°F). Mechanical and corrosion resistance, similar to but better than 304 SS. Very good heat resistance. This alloy contains 25% Cr, 20% Ni. Not as ductile as 304 SS.
Inconel 600
Maximum temperature: 1177°C (2150°F) Continuous; 1260°C (2300°F) Intermittent. Similar to Alloy 600 with the addition of aluminum for outstanding oxidation resistance. Designed for high temperature corrosion resistance. This material is good in carburizing environments, and has good creep rupture strength. Do not use in vacuum furnaces! Susceptible to intergranular attack by prolonged heating in 538° to 760°C (1000° to 1400°F) temperature range.
Chemical Composition of Stainless Steel Sheath
Sheath Material | Chemical Composition | Max. Temp. In Air | Melting Temp. | |||||||
C | Si | Mn | P | S | Cr | Ni | Others | |||
SS304 | ≤0.07 | ≤1.00 | ≤2.00 | ≤0.035 | ≤0.03 | 17-19 | 8-11 | - | 900℃ | 1405℃ |
SS321 | ≤0.12 | ≤1.00 | ≤2.00 | ≤0.035 | ≤0.03 | 17-19 | 8-11 | 5(C%-0.02)~0.08 | 870℃ | 1400℃ |
SS316 | ≤0.08 | ≤1.00 | ≤2.00 | ≤0.035 | ≤0.03 | 16-19 | 11-14 | Mo: 1.8-2.5 | 925℃ | 1370℃ |
SS310 | ≤0.08 | ≤1.00 | ≤2.00 | ≤0.035 | ≤0.03 | 24-26 | 19-22 | Ti: 5C%-0.07 | 1090℃ | 1405℃ |
INC600 | ≤0.15 | ≤0.50 | ≤1.00 | ≤0.030 | ≤0.015 | 14-17 | >72 | Fe: 6-10, Cu: <0 | 1090℃ | 1400℃ |
Sheath material | Sheath OD (mm) | Wall Thickness (mm) | Wire Dia. (mm) | Coil Length(m) |
SS304 SS321 SS316 SS310 INC600 | 0.5 | 0.05-0.10 | 0.08-0.12 | 200 |
1.0 | 0.10-0.20 | 0.15-0.20 | 200 | |
1.5 | 0.15-0.25 | 0.23-0.30 | 200 | |
1.6 | 0.16-0.26 | 0.26-0.36 | 200 | |
2.0 | 0.20-0.35 | 0.30-0.50 | 100 | |
2.4 | 0.24-0.36 | 0.36-0.41 | 100 | |
3.0 | 0.30-0.48 | 0.45-0.60 | 100 | |
3.2 | 0.32-0.58 | 0.48-0.68 | 100 | |
4.0 | 0.40-0.62 | 0.60-0.70 | 70 | |
4.5 | 0.45-0.68 | 0.68-0.77 | 70 | |
4.8 | 0.48-0.83 | 0.72-0.85 | 70 | |
6.0 | 0.60-1.08 | 0.90-1.10 | 50 | |
6.4 | 0.64-1.15 | 0.92-1.12 | 40 | |
8.0 | 0.80-1.44 | 1.20-1.40 | 30 | |
9.5 | 0.95-1.43 | 1.43-1.62 | 20 | |
10.0 | 1.00-1.50 | 1.50-1.70 | 20 | |
10.8 | 1.08-1.62 | 1.62-1.84 | 20 | |
12.7 | 1.27-1.90 | 1.91-2.05 | 10 |
Calibration Tolerance
Calibration | Tolerance | ||
Special Limits (Grade I) | Standard Limits (Grade II) | Temperature Range (℃) | |
K (Chromel vs Alumel) | 1.5°C or 0.4%t | 2.5°C or 0.75%t | -40~1000 |
J (Iron vs Constantan) | -40~750 | ||
E (Chromel vs Constantan) | -40~800 | ||
T (Copper vs Constantan) | 1°C or 0.75%t | -40~350 |
Order Code
Order Code:
Calibration | Sheath OD (mm) | Sheath Material | |||
Type K | Type J | Type E | Type T | ||
MIC-K-0.5-SS304 | MIC-J-0.5-SS304 | MIC-E-0.5-SS304 | MIC-T-0.5-SS304 | 0.5 | SS304 |
MIC-K-0.5-SS321 | MIC-J-0.5-SS321 | MIC-E-0.5-SS321 | MIC-T-0.5-SS321 | 0.5 | SS321 |
MIC-K-0.5-SS316 | MIC-J-0.5-SS316 | MIC-E-0.5-SS316 | MIC-T-0.5-SS316 | 0.5 | SS316 |
MIC-K-0.5-SS310 | MIC-J-0.5-SS310 | MIC-E-0.5-SS310 | MIC-T-0.5-SS310 | 0.5 | SS310 |
MIC-K-0.5-INC600 | MIC-J-0.5-INC600 | MIC-E-0.5-INC600 | MIC-T-0.5-INC600 | 0.5 | INC600 |
Order Example:
1. MIC-K-0.5-SS316, it means you order MI thermocouple cable is Simplex, type K, sheath dia: 0.5mm, sheath material: SS316
2. If you order MI thermocouple cable is Duplex, please change "MIC" to "MICD", it means "MICD-K-0.5-SS316"
3. If you order MI thermocouple cable is Triple, please change "MIC" to "MICT", it means "MICT-K-0.5-SS316"