Thermocouple & Thermometer & Temperature controller & G2500 Series intelligent digital display temperature controller

 

 
G2500 Series intelligent digital display temperature controller
     

sp-p908

sp-p908 sp-p908
G9
96¡Á96¡Á68mm
G8
48¡Á96¡Á60mm
G7
72¡Á72¡Á60mm
sp-p908 sp-p908
sp-p908
G6
96¡Á48¡Á60mm
G1
48¡Á48¡Á68mm
G16
80¡Á160¡Á68mm
Characteristic:

¡€Reliability. International invented meter power supply 85V~380V. That assures meters long-term use life, and applies to instable
electric network and diesel engine generating system.
¡€Anti-jamming. Products can work normally under circumstance that RKC,FUJI, OMRON, SHINKO, SHIMADEN usually in.
¡€ Quick AT self-tuning adaptive control and high precision of temperature control.
¡€Manual and automatic operation can be set by panel.
¡€Function of input signal and filtering (filtering quotiety 0~100)
¡€Arrears (password) lock function.( RKC, FUJI, and OMRON is without this function).
¡€User of zero declination can be adjustable.
¡€Power output percent (SV window) can switch display. (Digital display replaced light beam display, and RKC, FUJI, and OMRON
is without this function).
¡€Cooling output is controlled by PD (alarm 1). it adapts to water cooling, wind cooling, and adjust better than RKC, FUJI, and
OMRON.
¡€Timer: max timer function--100 hours, and can control facility working hour ( RKC, FUJI, and OMRON is without this function).
¡€Power output can be limited.(can be controlled up and down)
¡€Alarm: 7 kinds of alarm mode can be configured freely.
¡€Adopting single key to work (easy to work).


Meter's Technical Index

1) Indication precision: .3%FS character
2) Setting precision: .3%FS character
3) Input sampling cycle: 0.2 second
4) Relay Point Control Output: 250VAC 3A(block load) 250VAC 1A(Inductive load, cos¡é=0.4)
5) No point Voltage Control Output: ( SSR drives)12VDC, Max:40mA (short circuit protection)
6) Current & voltage output: 4-20mA, load resistance Max=500 Ohm.0-10VDC, load current ¡Ü10mA
7) Assistant power supply (feeding): 10V, 12V, 24V can be optional, load current¡Ü20mA
8) Alarm mode: on/off mode, lag 1¡æ (1¡æ) or 0.1¡æ
9) Alarm Output: Relay Point:250VAC 3A(resistance load) 250VAC1A(Inductive load, cos¡é=0.4)
10) Power Supply & Voltage: 85-240VAC,180-275VAC,50/60Hz,24VAC/DC,50/60Hz
11) Range of voltage: 85-275VAC,165-380VAC,22-26VAC/DC
12)Ambient Temperature:-5~50¡æ
13)Ambient Humidity: 80%RH
14) Weight: 230g
15)Power Loss: 4W
16) Insulation resistance: ¡Ý10meg-ohm(testing condition 500V)

Model:


Illustrate:G9-2500-R/E-A1-DR-A2-0-0

G9 size: 96¡Á96mm; 2500 is meter program series no; Ris relay output;E is thermocouple or platinum resistance input;
A1-DR is relay cooling output (PD control); A2 is the second circuit alarm (7 kinds of alarm mode can be configured freely);
0 is no feeding;0 is meter power supply 220V


Conntection:

Meter power supply
1-2 is 220V range:180V~380V, 1-3 is 110V range:85V-265V, 24V,48V¡À10% can supply also
4-5 Feeding (assistant power supply) 10V 24V
6-7-8 main output. 6-7 open 7-8 shut. no point voltage output 6+,7-
10-11-12 the first circuit alarm terminal£¬10-11 is shut terminal£¬11-12 is open terminal
13-14-15 the second circuit alarm terminal£¬13-14 is shut terminal£¬14-15 is open terminal
16-17-18 is thermal resistance input£¬16-17 is thermocouple input
4-5, 16-1 is connected with coloured wire on sensor when it is as pressure meter.

Meter power supply
1-2 is 220V range:180V~380V, 1-3 is 110V range:85V-265V, 24V,48V¡À10% can supply also
4-5 main output, no point voltage input 4+,5-
6-7 the first circuit alarm terminal
8-9 the second circuit alarm terminal
10-11 Feeding
16-17-18 is thermal resistance input£¬16-17 is thermocouple input
10-11-12-13 is connected with coloured wire on sensor when it is as pressure meter

Meter power supply
1-2 is 220V range:180V~380V, 1-3 is 110V range:85V-265V, 24V,48V¡À10% can supply also
4-5 Feeding (assistant power supply) 10V 24V
6-7 the first circuit alarm terminal
8-9-10 is thermal resistance input£¬8-9 is thermocouple input

Meter power supply
1-2 is 220V range:180V~380V, 1-3 is 110V range:85V-265V, 24V,48V¡À10% can supply also
4-5 Feeding (assistant power supply) 10V 24V
6-7-8 main output, 6-7 open 7-8 shut, no point voltage output 6+,7-
10-11 the second circuit alarm
12-13 the second circuit input signal
14-15 the first circuit alarm
16-17-18 the first circuit input signal is thermal resistance input£¬16-17 is thermocouple input

Alarm mode:

¡¡Alarm of upper limit declination
For instance: set value is 25¡æ£¬when alarm value is 2¡æ, alarm hysteresis is 1¡æ, temperature rises to 27¡æ(25¡æ+2¡æ) and begins to alarm, temperature returns to 26¡æ(25¡æ+2¡æ-1¡æ),alarm stops.

¡¡Alarm of lower limit declination
For instance: set value is 25¡æ£¬when alarm value is -2¡æ, alarm hysteresis is 1¡æ, temperature drops to 23¡æ(25¡æ-2¡æ) and begins to alarm, temperature rises to 24¡æ(25¡æ-2¡æ+1¡æ),alarm stops.

¡¡Alarm of upper limit absolute value
For instance: set value is 25¡æ£¬when alarm value is 27¡æ, alarm hysteresis is 1¡æ, temperature rises to 27¡æ and begins to alarm, temperature returns to 26¡æ(27¡æ-1¡æ),alarm stops.

¡¡Alarm of lower limit absolute value
For instance: set value is 25¡æ£¬when alarm value is 23¡æ, alarm hysteresis is 1¡æ, temperature drops to 23¡æ and begins to alarm, temperature rises to 24¡æ(23¡æ+1¡æ),alarm stops.

¡¡Alarm of upper/lower limit
¡æ(25¡æ-2¡æ), that begins to alarm, then temperature returns to 26¡æ(25¡æ+1¡æ),or rises to 24¡æ,alarm stops.

¡¡Alarm of upper/lower limit range
For instance: set value is 25¡æ£¬when alarm value is 2¡æ, alarm hysteresis is 1¡æ, it begins to alarm when temperature is between 22¡æ(25¡æ-2¡æ+1¡æ) and28¡æ(25¡æ+2¡æ+1¡æ),when temperature returns below 22¡æ,or rises above 28¡æ,alarm stops.

¡¡Time alarm
For instance: if want heat system to work some time but nobody watches, you can choose this alarm mode. The time you can choose from 1¡ª5999 minutes. the alarm will work if time comes.

Explanation of alarm collocation and choice of alarm mode:
choice of alarm mode
No Alarm
Alarm of upper/lower limit range
Alarm of upper limir declination
Cooling output, AL2 without
Alarm of lower limir declination
Timer alarm
*AL2 has this function but AL1 not.
Alarm of upper limir absoute value
Alarm of lower limir absoute value
upper/lower limir alarm
Choice of input/output signal
choice of output type
Solid state relay, 12V, ¡Ü40mA
Relay 250V, 3A(resistance load
silicon control, zero cross signa
current and voltage output 0-20mA or 4-20mA
10V or 1-5V and etc

choice of input signal
Pv input type
range
Thermocouple
K
0-1370¡æ
0-2500 0F
J
0-1000¡æ
0-1800 0F
R
0-1760¡æ
0-3200 0F
B
0-1820¡æ
0-3300 0F
S
0-1600¡æ
0-3200 0F
E
0-1000¡æ
0-1800 0F
Thermal resistance
Pt100
-199.9-850¡æ
-199.9-999.9 0F
Jpt100
-199.9-500.0¡æ
-199.9-900.0 0F
Voltage
0-1V
-199.9-5999
0-5V
-199.9-5999
1-5V
-199.9-5999
0-10V
-199.9-5999
1-10
-199.9-5999
MV/V
1.5mV/V
-199.9-5999
2mv/v
-199.9-5999
3.3mV/V
-199.9-5999
Current
0-20mA
-199.9-5999
4-20mA
-199.9-5999
Voltage transformer
0-200V
Current transformer
5A~
0-5999
proximity switch
NPN
-199.9-5999
PNP
-199.9-5999

choice of input type
Jpt100
Pt100
T type thermo-couple
B type thermo-couple
E type thermo-couple
K type thermo-couple
S type thermo-couple
J type thermo-couple
Current input or voltage input
Pressure meters, tachometers, power meters, frequency meters input